600V Quadruplex Conductor URD Cable

Application

Directly buried or installed in ducts for 600 volt secondary distribution.

·Cable in Duct (CIC)

·Abrasion Resistant

Construction

Concentric stranded or compressed 1350-H19 aluminum conductors, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Three phase and one neutral conductor cabled together (LH lay) or parallel if so specified. Black neutrals may be specified if desired.

Specification

ASTM B-230, B-231 and ICEA S-66-524
UL Standard 854 for type USE
Federal Specification JC-30B NEC

Code Name

Phase Conductor

Neutral

Single Phase Conductor(in)

Outside diameter(in)

Weight Per 1000ft (lbls)

Ampacity

Size AWG

Strand

Insulation Thickness (mls)

Size AWG

Strand

Insulation Thickness (mls)

Direct Burial

In Duct

Tulsa

4

7/w

60

4

7/w

60

.345

.833

258

119

85

Dyke

2

7/w

60

4

7/w

60

.403

.938

346

153

115

Wittenberg

2

7/w

60

2

7/w

60

.403

.973

375

153

115

Notre Dame

1/0

19/w

80

2

7/w

60

.522

1.188

541

198

150

Purdue

1/0

19/w

80

1/0

19/w

80

.522

1.260

596

198

150

Syracuse

2/0

19/w

80

1/0

19/w

80

.566

1.316

664

225

170

Lafayette

2/0

19/w

80

2/0

19/w

80

.566

1.367

720

225

170

Swarthmore

3/0

19/w

80

1/0

19/w

80

.616

1.430

805

250

195

Davidson

3/0

19/w

80

3/0

19/w

80

.616

1.487

874

250

195

Wake Forest

4/0

19/w

80

2/0

19/w

80

.672

1.560

979

290

225

Earlham

4/0

19/w

80

4/0

19/w

80

.672

1.623

1066

290

225

REQUEST A QUOTE

Get the minimum offer free of charge, please fill in the following information to tell us (confidential information, not open to the public)

TELEPHONE:

0086-371-68665329

ADD:

No.18 Building, The National University Science Park of Henan Province,No.283 Xisanhuan Road,Zhengzhou, China.

CONTACT US

We keep your information strictly confidential and will contact you within 24 hours. Please fill it out safely.