600V Triplex Conductor URD Cable

Application

Directly buried or installed in ducts for 600 volt secondary distribution.

·Cable in Duct(CIC)

·Abrasion Resistant

Construction

Concentric stranded or compressed 1350-H19 aluminum conductors, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Two phase and one neutral conductor twisted together (LH lay) or parallel if so specified. Black neutrals may be specified if desired.

Specification

ASTM B-230, B-231 and ICEA S-66-524
UL Standard 854 for type USE
Federal Specification JC-30B NEC

Code Name

Phase Conductor

Neutral

Single Phase Conductor (in)

Outside diameter (in)

Weight Per 1000ft (lbls)

Ampacity


Size AWG

Strand

Insulation Thickness (mls)

Size AWG

Strand

Insulation Thickness (mls)




Direct Burial

In Duct

Erksine

6

7/w

60

6

7/w

60

.299

.646

143

95

70

Vassar

4

7/w

60

4

7/w

60

.345

.754

203

125

90

Stephens

2

7/w

60

4

7/w

60

.403

.842

264

165

120

Ramapo

2

7/w

60

2

7/w

60

.403

.874

294

165

120

Brenau

1/0

19/w

80

2

7/w

60

.522

1.064

408

215

160

Bergen

1/0

19/w

80

1/0

19/w

80

.522

1.133

465

215

160

Converse

2/0

19/w

80

1/0

19/w

80

.566

1.174

502

245

180

Hunter

2/0

19/w

80

2/0

19/w

80

.566

1.228

560

245

180

Hollins

3/0

19/w

80

1/0

19/w

80

.616

1.276

606

280

205

Rockland

3/0

19/w

80

3/0

19/w

80

.616

1.336

678

280

205

Sweetbriar

4/0

19/w

80

2/0

19/w

80

.672

1.389

730

315

240

REQUEST A QUOTE

Get the minimum offer free of charge, please fill in the following information to tell us (confidential information, not open to the public)

TELEPHONE:

0086-371-68665329

ADD:

No.18 Building, The National University Science Park of Henan Province,No.283 Xisanhuan Road,Zhengzhou, China.

CONTACT US

We keep your information strictly confidential and will contact you within 24 hours. Please fill it out safely.